Fire Alarm System Drawings

Security and Access Control Systems (SACS) for Critical Security Areas

Special areas like Airports, Port Trusts, Naval Base, Military base, Telecom buildings, Refinery, Petroleum handling areas etc. needed highly sophisticated security and access control system. It provides safety and security for both men and equipment the area handling. Here is the specification and installation methods for SACS.

Typical Mounting Details Of Fire Alarm Detectors

These typical drawings show how to install smoke detectors and heat detectors used in Fire Alarm system on false ceiling. The installation shall be as per the relevant section in the contract specification and drawing has the following major points: Smoke detector mounted on false ceiling with the help of loop in box; Firetuff or equivalent cable run under the RCC slab clipped to the soffit; Cable size shall be 2 core 1.5 sq. mm copper; Cable has to be looped to the detector and tied as shown in the drawing.

Typical Mounting Details Of Fire Alarm Break Glass Manual Call Point

These drawings show how to install Fire Alarm Break Glass (BG) or Manual Call Point (MCP) on walls. It has to be mounted on back box installed in the wall. This box (embedded or exposed as specified in the concerned section of the specification) has to be connected through GI / PVC conduit that will have the Firetuff or equivalent cable to be looped for other detectors.