Multicore Cable Installation

 

 

Method of Electrical Earthing And Bonding Multicore Cables

The metallic sheath and armour of multicore cables shall be bonded together and earthed.

Cable earthing conductors shall be copper strip with appropriate section laid in formed cable trenches or ducts, or fixed to walls, concrete or steel work, by means of clamps or claw type cleats, appropriately secured into suitable wall plugs or tapped holes. The spacing of fixings shall not be greater than 1 m. Where earth strip is buried or laid in positions in which there is danger of corrosion it shall be provided with a corrosion-proof serving of extruded thermo-plastic or self-adhesive PVC tape which for short lengths may be hand applied on Site.